| − | == WHAT | + | == WHAT Reference WHO=1 == |
{| class="wikitable" style="float:left;" | {| class="wikitable" style="float:left;" | ||
! style="text-align:left;"| Value | ! style="text-align:left;"| Value | ||
| Line 119: | Line 119: | ||
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|30 | |30 | ||
| − | |Dimmer | + | |Dimmer up to next 10% step |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| − | |30# | + | |30#p#s |
| − | |Dimmer | + | |Dimmer p% up with s seconds (0..254) dimming time<br>If dimmer was off before, turns on to p%<br>A value of "0" seconds will use last used dimming time |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|31 | |31 | ||
| − | |Dimmer | + | |Dimmer down to previous 10% step |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| − | |31# | + | |31#p#s |
| − | |Dimmer | + | |Dimmer p% down with s seconds (0..254) dimming time<br>If dimmer was off before, turns on to p%<br>A value of "0" seconds will use last used dimming time |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|1000 | |1000 | ||
Revision as of 14:18, 2 November 2015
Standard Message *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful for door opener etc.) *1*29*23## Let light 23 blink for 5 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next level (+10%)
Status Request *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
WHAT Reference WHO=1
| Value | Description |
|---|---|
| 0 | OFF |
| 0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time |
| 1 | ON If dimmer: ON with last percentage |
| 1#x | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time |
| 2 | Set dimmer to 20% |
| 3 | Set dimmer to 30% |
| 4 | Set dimmer to 40% |
| 5 | Set dimmer to 50% |
| 6 | Set dimmer to 60% |
| 7 | Set dimmer to 70% |
| 8 | Set dimmer to 80% |
| 9 | Set dimmer to 90% |
| 10 | Set dimmer to 100% |
| 11 | ON for 1 min |
| 12 | ON for 2 min |
| 13 | ON for 3 min |
| 14 | ON for 4 min |
| 15 | ON for 5 min |
| 16 | ON for 15 min |
| 17 | ON for 30 sec |
| 18 | ON for 0.5 sec (useful as a push button) |
| 20 | Blinking with a frequency of 0.5 sec |
| 21 | Blinking with a frequency of 1 sec |
| 22 | Blinking with a frequency of 1.5 sec |
| 23 | Blinking with a frequency of 2 sec |
| 24 | Blinking with a frequency of 2.5 sec |
| 25 | Blinking with a frequency of 3 sec |
| 26 | Blinking with a frequency of 3.5 sec |
| 27 | Blinking with a frequency of 4 sec |
| 28 | Blinking with a frequency of 4.5 sec |
| 29 | Blinking with a frequency of 5 sec |
| 30 | Dimmer up to next 10% step |
| 30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% A value of "0" seconds will use last used dimming time |
| 31 | Dimmer down to previous 10% step |
| 31#p#s | Dimmer p% down with s seconds (0..254) dimming time If dimmer was off before, turns on to p% A value of "0" seconds will use last used dimming time |
| 1000 | Command translation triggered by push buttons. Read only, visible in monitor session. *1*1000#WHAT*WHERE## launches *1*WHAT*WHERE## |
| Dimension | Info |
|---|---|
| speed | 0..255 (0=now, 255=slowest) |
| step | one step = 10% of dimmer |
| WHERE | Address |
|---|---|
| 0 | General |
| 1..9 | Environment 1 to 9 |
| 11..99 | Light point 1.1 to 9.9 |
| 0110..0915 | Light point 1.10 to 9.15 |
| #1..#9 | Group 1 to 9 |