| + | == Standard Messages == | ||
| − | == Standard | + | === Standard Command === |
| + | Syntax: '''<tt>*WHO*WHAT*WHERE##</tt><br>''' | ||
| + | Examples: | ||
| + | <pre> | ||
| + | *1*1*23## Turn on light 23 | ||
| + | *1*0*23## Turn off light 23 | ||
| + | *1*7*45## Set dimmer 45 to 70% | ||
| + | *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) | ||
| + | *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) | ||
| + | *1*30*45## Set dimmer 45 up to next 10% step | ||
| + | </pre> | ||
| − | + | === Standard Request === | |
| − | + | Syntax: '''<tt>*#WHO*WHERE##</tt><br>''' | |
| − | * | ||
| − | * | ||
| − | == | + | Sending a Status Request to the gateway results in a Standard Message reply. |
| − | + | <pre> | |
| − | + | *#1*23## Request status of light 23 | |
| − | --- | + | *#1*45## Request status of light 45 |
| − | + | *#1*37## Request status of light 37 | |
| − | + | </pre> | |
| − | + | That 45 is a dimmer, we might realize when we get another reply than 0 or 1. | |
| − | + | ||
| − | + | === Standard Command Reference WHAT (WHO=1) === | |
| − | + | {| class="wikitable" | |
| − | + | ! style="text-align:left;"| Value | |
| − | + | ! style="text-align:left;"| Description | |
| − | + | |- | |
| − | + | |0 | |
| − | + | |OFF | |
| − | + | |- style="vertical-align:top;" | |
| − | + | |0#s | |
| − | + | |Turn OFF dimmer with s seconds (0..254) dimming time<br>to arrive at OFF<br>A value of "0" seconds will use last used dimming time | |
| − | + | |- style="vertical-align:top;" | |
| − | + | |1 | |
| − | + | |ON<br>If dimmer: ON with last percentage | |
| − | + | |- style="vertical-align:top;" | |
| − | + | |1#s | |
| − | + | |Turn ON dimmer with s seconds (0..254) dimming time<br>to arrive at last percentage of dimmer<br>A value of "0" seconds will use last used dimming time | |
| − | + | |- | |
| − | + | |2 | |
| − | + | |Set dimmer to 20% | |
| − | + | |- | |
| − | + | |3 | |
| − | + | |Set dimmer to 30% | |
| − | + | |- | |
| − | + | |4 | |
| − | + | |Set dimmer to 40% | |
| − | + | |- | |
| − | + | |5 | |
| − | + | |Set dimmer to 50% | |
| − | 30# | + | |- |
| − | + | |6 | |
| − | + | |Set dimmer to 60% | |
| − | + | |- | |
| − | </ | + | |7 |
| + | |Set dimmer to 70% | ||
| + | |- | ||
| + | |8 | ||
| + | |Set dimmer to 80% | ||
| + | |- | ||
| + | |9 | ||
| + | |Set dimmer to 90% | ||
| + | |- | ||
| + | |10 | ||
| + | |Set dimmer to 100% | ||
| + | |- | ||
| + | |11 | ||
| + | |ON for 1 min | ||
| + | |- | ||
| + | |12 | ||
| + | |ON for 2 min | ||
| + | |- | ||
| + | |13 | ||
| + | |ON for 3 min | ||
| + | |- | ||
| + | |14 | ||
| + | |ON for 4 min | ||
| + | |- | ||
| + | |15 | ||
| + | |ON for 5 min | ||
| + | |- | ||
| + | |16 | ||
| + | |ON for 15 min | ||
| + | |- | ||
| + | |17 | ||
| + | |ON for 30 sec | ||
| + | |- | ||
| + | |18 | ||
| + | |ON for 0.5 sec | ||
| + | |- | ||
| + | |20 | ||
| + | |Blinking with a frequency of 0.5 sec | ||
| + | |- | ||
| + | |21 | ||
| + | |Blinking with a frequency of 1 sec | ||
| + | |- | ||
| + | |22 | ||
| + | |Blinking with a frequency of 1.5 sec | ||
| + | |- | ||
| + | |23 | ||
| + | |Blinking with a frequency of 2 sec | ||
| + | |- | ||
| + | |24 | ||
| + | |Blinking with a frequency of 2.5 sec | ||
| + | |- | ||
| + | |25 | ||
| + | |Blinking with a frequency of 3 sec | ||
| + | |- | ||
| + | |26 | ||
| + | |Blinking with a frequency of 3.5 sec | ||
| + | |- | ||
| + | |27 | ||
| + | |Blinking with a frequency of 4 sec | ||
| + | |- | ||
| + | |28 | ||
| + | |Blinking with a frequency of 4.5 sec | ||
| + | |- | ||
| + | |29 | ||
| + | |Blinking with a frequency of 5 sec | ||
| + | |- style="vertical-align:top;" | ||
| + | |30 | ||
| + | |Dimmer up to next 10% step | ||
| + | |- style="vertical-align:top;" | ||
| + | |30#p#s | ||
| + | |Dimmer p% up with s seconds (0..254) dimming time<br>If dimmer was off before, turns on to p%<br>Dimmer arrives max. at 100%<br>A value of "0" seconds will use last used dimming time | ||
| + | |- style="vertical-align:top;" | ||
| + | |31 | ||
| + | |Dimmer down to previous 10% step | ||
| + | |- style="vertical-align:top;" | ||
| + | |31#p#s | ||
| + | |Dimmer p% down with s seconds (0..254) dimming time<br>Lowest percentage the dimmer arrives is 1%<br>A value of "0" seconds will use last used dimming time | ||
| + | |- style="vertical-align:top;" | ||
| + | |1000# | ||
| + | |Internal Command translation, visible in monitor session only. | ||
| + | |} | ||
| + | |||
| + | |||
| + | |||
| + | == Parameter Messages == | ||
| + | |||
| + | === Parameter Command === | ||
| + | Syntax: '''<tt>*#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##</tt><br>''' | ||
| + | Examples: | ||
| + | <pre> | ||
| + | *#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s | ||
| + | *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s | ||
| + | *#1*23*#9*1## Set max working hours of light 23 to one hour | ||
| + | </pre> | ||
| + | |||
| + | === Parameter Request === | ||
| + | Syntax: '''<tt>*#WHO*WHERE*#PARAMETER##</tt><br>''' | ||
| + | Examples: | ||
| + | <pre> | ||
| + | *#1*43*#2## Get remaining countdown time OF LIGHT 43 | ||
| + | *#1*12*#8## Get the total amount of operation hours, light 12 was powered on | ||
| + | </pre> | ||
| + | |||
| + | === Parameter Reference (WHO=1) === | ||
| + | {| class="wikitable" | ||
| + | ! style="text-align:left;"| Parameter | ||
| + | ! style="text-align:left;"| Description | ||
| + | |- style="vertical-align:top;" | ||
| + | |#1 | ||
| + | |Returns dimmer status <br><tt>*#1*WHERE*1*PERCENTAGE*DIMMINGTIME##</tt> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#1*p*s | ||
| + | |Set dimmer p% up with s seconds (0..254) dimming time<br><span style="color:red">Didn't work for me</span> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#2 | ||
| + | |Returns the remaining countdown time until light switches of<br><tt>*#1*WHERE*2*HOURS*MINUTES*SECONDS##</tt> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#2*h*m*s | ||
| + | |Turn ON light for a certain amount of time (countdown timer) <br>Values for hours, minutes, seconds are integer | ||
| + | |- style="vertical-align:top;" | ||
| + | |#3 | ||
| + | |Returns some "Required Only ON Light ???"<br><span style="color:red">Didn't work for me</span> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#8 | ||
| + | |Returns the total amount of operation hours, the light was powered on<br><tt>*#1*WHERE*8*HOURS##</tt> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#9 | ||
| + | |Returns Max amount of hours working time lamp<br><span style="color:red">Didn't work for me</span> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#9*h | ||
| + | |Set max. 'working time' in hours<br>Values for hours are integer<br><span style="color:red">Didn't work for me</span> | ||
| + | |} | ||
| + | |||
| + | |||
| + | |||
| + | {| style="width:100%; border:1px solid #EEEEEE; background-color:#FFFFCC" | ||
| + | |style="text-align:left;"|[[WHO=0 - Scenarios]] | ||
| + | |style="text-align:center;"|[[OWN_OpenWebNet_Language_Reference#WHO_Table|WHO Table]] | ||
| + | |style="text-align:right;"|[[WHO=2 - Automation]] | ||
| + | |} | ||
Latest revision as of 19:27, 2 November 2015
Contents
Standard Messages
Standard Command
Syntax: *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next 10% step
Standard Request
Syntax: *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
Standard Command Reference WHAT (WHO=1)
| Value | Description |
|---|---|
| 0 | OFF |
| 0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time |
| 1 | ON If dimmer: ON with last percentage |
| 1#s | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time |
| 2 | Set dimmer to 20% |
| 3 | Set dimmer to 30% |
| 4 | Set dimmer to 40% |
| 5 | Set dimmer to 50% |
| 6 | Set dimmer to 60% |
| 7 | Set dimmer to 70% |
| 8 | Set dimmer to 80% |
| 9 | Set dimmer to 90% |
| 10 | Set dimmer to 100% |
| 11 | ON for 1 min |
| 12 | ON for 2 min |
| 13 | ON for 3 min |
| 14 | ON for 4 min |
| 15 | ON for 5 min |
| 16 | ON for 15 min |
| 17 | ON for 30 sec |
| 18 | ON for 0.5 sec |
| 20 | Blinking with a frequency of 0.5 sec |
| 21 | Blinking with a frequency of 1 sec |
| 22 | Blinking with a frequency of 1.5 sec |
| 23 | Blinking with a frequency of 2 sec |
| 24 | Blinking with a frequency of 2.5 sec |
| 25 | Blinking with a frequency of 3 sec |
| 26 | Blinking with a frequency of 3.5 sec |
| 27 | Blinking with a frequency of 4 sec |
| 28 | Blinking with a frequency of 4.5 sec |
| 29 | Blinking with a frequency of 5 sec |
| 30 | Dimmer up to next 10% step |
| 30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% Dimmer arrives max. at 100% A value of "0" seconds will use last used dimming time |
| 31 | Dimmer down to previous 10% step |
| 31#p#s | Dimmer p% down with s seconds (0..254) dimming time Lowest percentage the dimmer arrives is 1% A value of "0" seconds will use last used dimming time |
| 1000# | Internal Command translation, visible in monitor session only. |
Parameter Messages
Parameter Command
Syntax: *#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##
Examples:
*#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s *#1*23*#9*1## Set max working hours of light 23 to one hour
Parameter Request
Syntax: *#WHO*WHERE*#PARAMETER##
Examples:
*#1*43*#2## Get remaining countdown time OF LIGHT 43 *#1*12*#8## Get the total amount of operation hours, light 12 was powered on
Parameter Reference (WHO=1)
| Parameter | Description |
|---|---|
| #1 | Returns dimmer status *#1*WHERE*1*PERCENTAGE*DIMMINGTIME## |
| #1*p*s | Set dimmer p% up with s seconds (0..254) dimming time Didn't work for me |
| #2 | Returns the remaining countdown time until light switches of *#1*WHERE*2*HOURS*MINUTES*SECONDS## |
| #2*h*m*s | Turn ON light for a certain amount of time (countdown timer) Values for hours, minutes, seconds are integer |
| #3 | Returns some "Required Only ON Light ???" Didn't work for me |
| #8 | Returns the total amount of operation hours, the light was powered on *#1*WHERE*8*HOURS## |
| #9 | Returns Max amount of hours working time lamp Didn't work for me |
| #9*h | Set max. 'working time' in hours Values for hours are integer Didn't work for me |
| WHO=0 - Scenarios | WHO Table | WHO=2 - Automation |