Difference between revisions of "WHO=1 - Lighting"
Jump to navigation
Jump to search
(71 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
− | ==== Standard | + | == Standard Messages == |
+ | |||
+ | === Standard Command === | ||
+ | Syntax: '''<tt>*WHO*WHAT*WHERE##</tt><br>''' | ||
Examples: | Examples: | ||
<pre> | <pre> | ||
Line 5: | Line 8: | ||
*1*0*23## Turn off light 23 | *1*0*23## Turn off light 23 | ||
*1*7*45## Set dimmer 45 to 70% | *1*7*45## Set dimmer 45 to 70% | ||
− | *1*18*37## Turn on light 37 for 0.5 sec (useful for door opener etc.) | + | *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) |
− | *1* | + | *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) |
− | *1*30*45## Set dimmer 45 up to next | + | *1*30*45## Set dimmer 45 up to next 10% step |
</pre> | </pre> | ||
− | ==== | + | === Standard Request === |
+ | Syntax: '''<tt>*#WHO*WHERE##</tt><br>''' | ||
+ | |||
Sending a Status Request to the gateway results in a Standard Message reply. | Sending a Status Request to the gateway results in a Standard Message reply. | ||
<pre> | <pre> | ||
Line 17: | Line 22: | ||
*#1*37## Request status of light 37 | *#1*37## Request status of light 37 | ||
</pre> | </pre> | ||
− | That 45 is a dimmer, we might realize when we get another reply than 0 or 1. | + | That 45 is a dimmer, we might realize when we get another reply than 0 or 1. |
− | + | === Standard Command Reference WHAT (WHO=1) === | |
− | == WHAT | + | {| class="wikitable" |
− | {| class="wikitable | ||
! style="text-align:left;"| Value | ! style="text-align:left;"| Value | ||
! style="text-align:left;"| Description | ! style="text-align:left;"| Description | ||
Line 28: | Line 32: | ||
|OFF | |OFF | ||
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
− | |0# | + | |0#s |
− | |Turn OFF dimmer with | + | |Turn OFF dimmer with s seconds (0..254) dimming time<br>to arrive at OFF<br>A value of "0" seconds will use last used dimming time |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|1 | |1 | ||
|ON<br>If dimmer: ON with last percentage | |ON<br>If dimmer: ON with last percentage | ||
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
− | |1# | + | |1#s |
− | |Turn ON dimmer with | + | |Turn ON dimmer with s seconds (0..254) dimming time<br>to arrive at last percentage of dimmer<br>A value of "0" seconds will use last used dimming time |
|- | |- | ||
|2 | |2 | ||
Line 86: | Line 90: | ||
|- | |- | ||
|18 | |18 | ||
− | |ON for 0.5 sec | + | |ON for 0.5 sec |
− | |||
− | |||
− | |||
|- | |- | ||
|20 | |20 | ||
− | |Blinking | + | |Blinking with a frequency of 0.5 sec |
|- | |- | ||
|21 | |21 | ||
− | |Blinking | + | |Blinking with a frequency of 1 sec |
|- | |- | ||
|22 | |22 | ||
− | |Blinking | + | |Blinking with a frequency of 1.5 sec |
|- | |- | ||
|23 | |23 | ||
− | |Blinking | + | |Blinking with a frequency of 2 sec |
|- | |- | ||
|24 | |24 | ||
− | |Blinking | + | |Blinking with a frequency of 2.5 sec |
|- | |- | ||
|25 | |25 | ||
− | |Blinking | + | |Blinking with a frequency of 3 sec |
|- | |- | ||
|26 | |26 | ||
− | |Blinking | + | |Blinking with a frequency of 3.5 sec |
|- | |- | ||
|27 | |27 | ||
− | |Blinking | + | |Blinking with a frequency of 4 sec |
|- | |- | ||
|28 | |28 | ||
− | |Blinking | + | |Blinking with a frequency of 4.5 sec |
|- | |- | ||
|29 | |29 | ||
− | |Blinking | + | |Blinking with a frequency of 5 sec |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|30 | |30 | ||
− | |Dimmer | + | |Dimmer up to next 10% step |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
− | |30# | + | |30#p#s |
− | |Dimmer | + | |Dimmer p% up with s seconds (0..254) dimming time<br>If dimmer was off before, turns on to p%<br>Dimmer arrives max. at 100%<br>A value of "0" seconds will use last used dimming time |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
|31 | |31 | ||
− | |Dimmer | + | |Dimmer down to previous 10% step |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
− | |31# | + | |31#p#s |
− | |Dimmer | + | |Dimmer p% down with s seconds (0..254) dimming time<br>Lowest percentage the dimmer arrives is 1%<br>A value of "0" seconds will use last used dimming time |
|- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
− | |1000 | + | |1000# |
− | |Command translation | + | |Internal Command translation, visible in monitor session only. |
|} | |} | ||
− | {| class="wikitable" style=" | + | |
− | ! style="text-align:left;"| | + | |
− | + | == Parameter Messages == | |
− | |- | + | |
− | | | + | === Parameter Command === |
− | |0.. | + | Syntax: '''<tt>*#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##</tt><br>''' |
− | |- | + | Examples: |
− | | | + | <pre> |
− | | | + | *#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s |
+ | *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s | ||
+ | *#1*23*#9*1## Set max working hours of light 23 to one hour | ||
+ | </pre> | ||
+ | |||
+ | === Parameter Request === | ||
+ | Syntax: '''<tt>*#WHO*WHERE*#PARAMETER##</tt><br>''' | ||
+ | Examples: | ||
+ | <pre> | ||
+ | *#1*43*#2## Get remaining countdown time OF LIGHT 43 | ||
+ | *#1*12*#8## Get the total amount of operation hours, light 12 was powered on | ||
+ | </pre> | ||
+ | |||
+ | === Parameter Reference (WHO=1) === | ||
+ | {| class="wikitable" | ||
+ | ! style="text-align:left;"| Parameter | ||
+ | ! style="text-align:left;"| Description | ||
+ | |- style="vertical-align:top;" | ||
+ | |#1 | ||
+ | |Returns dimmer status <br><tt>*#1*WHERE*1*PERCENTAGE*DIMMINGTIME##</tt> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#1*p*s | ||
+ | |Set dimmer p% up with s seconds (0..254) dimming time<br><span style="color:red">Didn't work for me</span> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#2 | ||
+ | |Returns the remaining countdown time until light switches of<br><tt>*#1*WHERE*2*HOURS*MINUTES*SECONDS##</tt> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#2*h*m*s | ||
+ | |Turn ON light for a certain amount of time (countdown timer) <br>Values for hours, minutes, seconds are integer | ||
+ | |- style="vertical-align:top;" | ||
+ | |#3 | ||
+ | |Returns some "Required Only ON Light ???"<br><span style="color:red">Didn't work for me</span> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#8 | ||
+ | |Returns the total amount of operation hours, the light was powered on<br><tt>*#1*WHERE*8*HOURS##</tt> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#9 | ||
+ | |Returns Max amount of hours working time lamp<br><span style="color:red">Didn't work for me</span> | ||
+ | |- style="vertical-align:top;" | ||
+ | |#9*h | ||
+ | |Set max. 'working time' in hours<br>Values for hours are integer<br><span style="color:red">Didn't work for me</span> | ||
|} | |} | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
Latest revision as of 19:27, 2 November 2015
Contents
Standard Messages
Standard Command
Syntax: *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next 10% step
Standard Request
Syntax: *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
Standard Command Reference WHAT (WHO=1)
Value | Description |
---|---|
0 | OFF |
0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time |
1 | ON If dimmer: ON with last percentage |
1#s | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time |
2 | Set dimmer to 20% |
3 | Set dimmer to 30% |
4 | Set dimmer to 40% |
5 | Set dimmer to 50% |
6 | Set dimmer to 60% |
7 | Set dimmer to 70% |
8 | Set dimmer to 80% |
9 | Set dimmer to 90% |
10 | Set dimmer to 100% |
11 | ON for 1 min |
12 | ON for 2 min |
13 | ON for 3 min |
14 | ON for 4 min |
15 | ON for 5 min |
16 | ON for 15 min |
17 | ON for 30 sec |
18 | ON for 0.5 sec |
20 | Blinking with a frequency of 0.5 sec |
21 | Blinking with a frequency of 1 sec |
22 | Blinking with a frequency of 1.5 sec |
23 | Blinking with a frequency of 2 sec |
24 | Blinking with a frequency of 2.5 sec |
25 | Blinking with a frequency of 3 sec |
26 | Blinking with a frequency of 3.5 sec |
27 | Blinking with a frequency of 4 sec |
28 | Blinking with a frequency of 4.5 sec |
29 | Blinking with a frequency of 5 sec |
30 | Dimmer up to next 10% step |
30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% Dimmer arrives max. at 100% A value of "0" seconds will use last used dimming time |
31 | Dimmer down to previous 10% step |
31#p#s | Dimmer p% down with s seconds (0..254) dimming time Lowest percentage the dimmer arrives is 1% A value of "0" seconds will use last used dimming time |
1000# | Internal Command translation, visible in monitor session only. |
Parameter Messages
Parameter Command
Syntax: *#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##
Examples:
*#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s *#1*23*#9*1## Set max working hours of light 23 to one hour
Parameter Request
Syntax: *#WHO*WHERE*#PARAMETER##
Examples:
*#1*43*#2## Get remaining countdown time OF LIGHT 43 *#1*12*#8## Get the total amount of operation hours, light 12 was powered on
Parameter Reference (WHO=1)
Parameter | Description |
---|---|
#1 | Returns dimmer status *#1*WHERE*1*PERCENTAGE*DIMMINGTIME## |
#1*p*s | Set dimmer p% up with s seconds (0..254) dimming time Didn't work for me |
#2 | Returns the remaining countdown time until light switches of *#1*WHERE*2*HOURS*MINUTES*SECONDS## |
#2*h*m*s | Turn ON light for a certain amount of time (countdown timer) Values for hours, minutes, seconds are integer |
#3 | Returns some "Required Only ON Light ???" Didn't work for me |
#8 | Returns the total amount of operation hours, the light was powered on *#1*WHERE*8*HOURS## |
#9 | Returns Max amount of hours working time lamp Didn't work for me |
#9*h | Set max. 'working time' in hours Values for hours are integer Didn't work for me |
WHO=0 - Scenarios | WHO Table | WHO=2 - Automation |