Difference between revisions of "WHO=1 - Lighting"
		
		
		
		
		
		
		Jump to navigation
		Jump to search
		
				
		
		
		
		
		
		
		
		
	
| (15 intermediate revisions by the same user not shown) | |||
| Line 135: | Line 135: | ||
| |- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| |1000# | |1000# | ||
| − | |Internal Command translation, visible in monitor session only. | + | |Internal Command translation, visible in monitor session only. | 
| |} | |} | ||
| + | |||
| + | |||
| == Parameter Messages == | == Parameter Messages == | ||
| Line 146: | Line 148: | ||
| *#1*43*#2*1*35*18##        Turn on light 43 for 1h:35m:18s | *#1*43*#2*1*35*18##        Turn on light 43 for 1h:35m:18s | ||
| *#1*44#4#03*#2*0*0*13##    Turn on light 44 of interface 03 for 13s | *#1*44#4#03*#2*0*0*13##    Turn on light 44 of interface 03 for 13s | ||
| − | *#1* | + | *#1*23*#9*1##              Set max working hours of light 23 to one hour | 
| </pre> | </pre> | ||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| − | |||
| === Parameter Request === | === Parameter Request === | ||
| Line 168: | Line 155: | ||
| Examples: | Examples: | ||
| <pre> | <pre> | ||
| − | *#1*43*#2 | + | *#1*43*#2##     Get remaining countdown time OF LIGHT 43 | 
| − | *#1* | + | *#1*12*#8## 	Get the total amount of operation hours, light 12 was powered on | 
| − | |||
| </pre> | </pre> | ||
| − | === Parameter  | + | === Parameter Reference (WHO=1) === | 
| {| class="wikitable"   | {| class="wikitable"   | ||
| ! style="text-align:left;"| Parameter | ! style="text-align:left;"| Parameter | ||
| Line 180: | Line 166: | ||
| |#1 | |#1 | ||
| |Returns dimmer status <br><tt>*#1*WHERE*1*PERCENTAGE*DIMMINGTIME##</tt> | |Returns dimmer status <br><tt>*#1*WHERE*1*PERCENTAGE*DIMMINGTIME##</tt> | ||
| + | |- style="vertical-align:top;" | ||
| + | |#1*p*s | ||
| + | |Set dimmer p% up with s seconds (0..254) dimming time<br><span style="color:red">Didn't work for me</span> | ||
| |- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| |#2 | |#2 | ||
| − | |Returns the remaining  | + | |Returns the remaining countdown time until light switches of<br><tt>*#1*WHERE*2*HOURS*MINUTES*SECONDS##</tt> | 
| + | |- style="vertical-align:top;" | ||
| + | |#2*h*m*s | ||
| + | |Turn ON light for a certain amount of time (countdown timer) <br>Values for hours, minutes, seconds are integer | ||
| |- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| |#3 | |#3 | ||
| − | |Required Only ON Light | + | |Returns some "Required Only ON Light ???"<br><span style="color:red">Didn't work for me</span> | 
| |- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| |#8 | |#8 | ||
| − | | | + | |Returns the total amount of operation hours, the light was powered on<br><tt>*#1*WHERE*8*HOURS##</tt> | 
| |- style="vertical-align:top;" | |- style="vertical-align:top;" | ||
| |#9 | |#9 | ||
| − | |Max working time lamp | + | |Returns Max amount of hours working time lamp<br><span style="color:red">Didn't work for me</span> | 
| + | |- style="vertical-align:top;" | ||
| + | |#9*h | ||
| + | |Set max. 'working time' in hours<br>Values for hours are integer<br><span style="color:red">Didn't work for me</span> | ||
| |} | |} | ||
Latest revision as of 19:27, 2 November 2015
Contents
Standard Messages
Standard Command
Syntax: *WHO*WHAT*WHERE##
Examples:
*1*1*23## Turn on light 23 *1*0*23## Turn off light 23 *1*7*45## Set dimmer 45 to 70% *1*18*37## Turn on light 37 for 0.5 sec (useful as push button for door opener etc.) *1*21*23## Let light 23 blink with a frequency of 1 sec (useful as a 'silent' alarm) *1*30*45## Set dimmer 45 up to next 10% step
Standard Request
Syntax: *#WHO*WHERE##
Sending a Status Request to the gateway results in a Standard Message reply.
*#1*23## Request status of light 23 *#1*45## Request status of light 45 *#1*37## Request status of light 37
That 45 is a dimmer, we might realize when we get another reply than 0 or 1.
Standard Command Reference WHAT (WHO=1)
| Value | Description | 
|---|---|
| 0 | OFF | 
| 0#s | Turn OFF dimmer with s seconds (0..254) dimming time to arrive at OFF A value of "0" seconds will use last used dimming time | 
| 1 | ON If dimmer: ON with last percentage | 
| 1#s | Turn ON dimmer with s seconds (0..254) dimming time to arrive at last percentage of dimmer A value of "0" seconds will use last used dimming time | 
| 2 | Set dimmer to 20% | 
| 3 | Set dimmer to 30% | 
| 4 | Set dimmer to 40% | 
| 5 | Set dimmer to 50% | 
| 6 | Set dimmer to 60% | 
| 7 | Set dimmer to 70% | 
| 8 | Set dimmer to 80% | 
| 9 | Set dimmer to 90% | 
| 10 | Set dimmer to 100% | 
| 11 | ON for 1 min | 
| 12 | ON for 2 min | 
| 13 | ON for 3 min | 
| 14 | ON for 4 min | 
| 15 | ON for 5 min | 
| 16 | ON for 15 min | 
| 17 | ON for 30 sec | 
| 18 | ON for 0.5 sec | 
| 20 | Blinking with a frequency of 0.5 sec | 
| 21 | Blinking with a frequency of 1 sec | 
| 22 | Blinking with a frequency of 1.5 sec | 
| 23 | Blinking with a frequency of 2 sec | 
| 24 | Blinking with a frequency of 2.5 sec | 
| 25 | Blinking with a frequency of 3 sec | 
| 26 | Blinking with a frequency of 3.5 sec | 
| 27 | Blinking with a frequency of 4 sec | 
| 28 | Blinking with a frequency of 4.5 sec | 
| 29 | Blinking with a frequency of 5 sec | 
| 30 | Dimmer up to next 10% step | 
| 30#p#s | Dimmer p% up with s seconds (0..254) dimming time If dimmer was off before, turns on to p% Dimmer arrives max. at 100% A value of "0" seconds will use last used dimming time | 
| 31 | Dimmer down to previous 10% step | 
| 31#p#s | Dimmer p% down with s seconds (0..254) dimming time Lowest percentage the dimmer arrives is 1% A value of "0" seconds will use last used dimming time | 
| 1000# | Internal Command translation, visible in monitor session only. | 
Parameter Messages
Parameter Command
Syntax: *#WHO*WHERE*#PARAMETER*VALUE1[*VALUE2...]##
Examples:
*#1*43*#2*1*35*18## Turn on light 43 for 1h:35m:18s *#1*44#4#03*#2*0*0*13## Turn on light 44 of interface 03 for 13s *#1*23*#9*1## Set max working hours of light 23 to one hour
Parameter Request
Syntax: *#WHO*WHERE*#PARAMETER##
Examples:
*#1*43*#2## Get remaining countdown time OF LIGHT 43 *#1*12*#8## Get the total amount of operation hours, light 12 was powered on
Parameter Reference (WHO=1)
| Parameter | Description | 
|---|---|
| #1 | Returns dimmer status *#1*WHERE*1*PERCENTAGE*DIMMINGTIME## | 
| #1*p*s | Set dimmer p% up with s seconds (0..254) dimming time Didn't work for me | 
| #2 | Returns the remaining countdown time until light switches of *#1*WHERE*2*HOURS*MINUTES*SECONDS## | 
| #2*h*m*s | Turn ON light for a certain amount of time (countdown timer) Values for hours, minutes, seconds are integer | 
| #3 | Returns some "Required Only ON Light ???" Didn't work for me | 
| #8 | Returns the total amount of operation hours, the light was powered on *#1*WHERE*8*HOURS## | 
| #9 | Returns Max amount of hours working time lamp Didn't work for me | 
| #9*h | Set max. 'working time' in hours Values for hours are integer Didn't work for me | 
| WHO=0 - Scenarios | WHO Table | WHO=2 - Automation | 